CC 2017-10-10_09e Reservoir No 2 Standby Generator MEMORANDUM TO: CITY COUNCIL FROM: BILL ROBESON, PUBLIC WORKS DIRECTOR BY: SHANE TAYLOR, UTILITIES MANAGER SUBJECT: CONSIDERATION OF AN APPROPRIATION OF FUNDS TO REPLACE THE EMERGENCY STANDBY GENERATOR LOCATED AT RESERVOIR NO. 2 ON HILLCREST DRIVE DATE: OCTOBER 10, 2017 SUMMARY OF ACTION: Approve funds to replace the generator at Reservoir No. 2. IMPACT ON FINANCIAL AND PERSONNEL RESOURCES: The replacement generator was not budgeted in FY 2017/18 and will reduce the General Fund balance by $25,000. RECOMMENDATION: It is recommended the City Council approve an appropriation of $25,000 from the unappropriated General Fund Balance to purchase a new standby generator and automatic transfer switch for the Reservoir No. 2 communication building. BACKGROUND: The radio communication building located at Reservoir No. 2 on Hillcrest Drive provides a secure location for the radios that serve the Arroyo Grande Police Department, Five Cities Fire Authority, and the Public Works Department. Radio communication is vital to daily operations. The existing standby generator is over 30 years old and no longer works. A temporary trailer mounted generator with manual start has been in place since the old generator stopped working during the February 2017 storm. It is vital during power outages that this building has power to continue radio communications. ANALYSIS OF ISSUES: The existing propane powered standby generator at Reservoir No. 2 needs to be replaced. A report was prepared by IRJ Engineers, Inc. detailing the requirements for the replacement generator and automatic transfer switch. The report also identified deficiencies in the current circuits that should also be corrected. The replacement and upgrade of equipment will provide a long term solution to the current and future power needs of this facility. Item 9.e. - Page 1 CITY COUNCIL CONSIDERATION OF AN APPROPRIATION OF FUNDS TO REPLACE THE EMERGENCY STANDBY GENERATOR LOCATED AT RESERVOIR NO. 2 ON HILLCREST DRIVE OCTOBER 10, 2017 PAGE 2 ALTERNATIVES: The following alternatives are provided for the Council’s consideration: 1. Authorize the appropriation of funds to purchase the new standby generator; 2. Do not authorize the appropriation of funds; 3. Provide direction to staff. ADVANTAGES: The radio communication building will have reliable power during power outages. DISADVANTAGES: The purchase and installation of the new standby generator will reduce the General Fund by $25,000. ENVIRONMENTAL REVIEW: The project is categorically exempt from the California Environmental Quality Act (CEQA) pursuant to CEQA Guidelines Section 15301 covering minor alteration of mechanical equipment. PUBLIC NOTIFICATION AND COMMENTS: The Agenda was posted at City Hall and on the City’s website in accordance with Government Code Section 54954.2. Attachment: 1. Letter Report from IRJ Engineers, Inc. dated September 5, 2017 2. Letter from MKN & Associates, Inc. regarding Design and Construction Phase Services dated September 15, 2017 3. Generator Sales Quotation from San Luis Powerhouse dated September 8, 2017 Item 9.e. - Page 2 OFFICERS JACK V. IVERS, P.E. STEVEN ROMOFSKY, P.E. JILL E. JOHNSON, P.E. IRJ ENGINEERS INC. MECHANICAL & ELECTRICAL ENGINEERS 2497 E. HARBOR BOULEVARD, SUITE 1 VENTURA, CALIFORNIA 93001-3933 TELE (805) 642-2355 FAX (805) 658-0623 MECHANICAL AND ELECTRICAL ENGINEERING SERVICES FURNISHED BY OR UNDER THE DIRECTION OF PROFESSIONAL ENGINEERS MEMBER OF THE AMERICAN COUNCIL OF ENGINEERING COMPANIES − CALIFORNIA September 5, 2017 Mr. J.J. Reichmuth Michael K. Nunley & Associates P.O. Box 1604 Arroyo Grande, California 93421 Re: City of Arroyo Grande Reservoir 2 Emergency Generator Replacement Letter Report Dear J.J.: We reviewed the existing emergency generator installation at Reservoir 2 on August 15, 2017. The following report describes our observations and recommendations. OBSERVATIONS The existing system is served by a 100-amp, 120/240V, single-phase, three-wire service from PG&E to a 100-amp, 2-pole meter/main circuit breaker enclosure mounted on the building exterior. There is an existing 120/240V, single-phase, three-wire, 4kW backup generator that supplies emergency power through a 30-amp, 1-pole circuit breaker mounted on the generator. The generator nameplate lists the rated amperes at 16.7. The 30-amp breaker is too large to provide overcurrent protection for the generator, and should have been a 2-pole device. It does not appear that the existing generator was properly sized for the loads that it supplied. The main circuit breaker and generator breaker supply the normal and emergency sources, respectively, to a 30-amp, 120V automatic transfer switch (ATS) located in the equipment room. It is unclear why a 1-pole, 2-wire ATS was selected for this installation. The 100-amp main circuit breaker does not provide code compliant overcurrent protection for the ATS when power is supplied by the utility. The feeder between the main circuit breaker and the ATS is 2-4AWG & 1-6AWGGround. The feeder between the generator breaker and the ATS is 2-12AWG & 1-12AWGGround. Although both the utility service and the generator are rated for 120/240V, single-phase, three-wire operation, they are both connected so that only one phase is used. It is very unusual to connect this equipment at 120V in lieu of 120/240V. The ATS load side feeds a 100-amp, 120/240V load center located inside the equipment room via 2-4AWG & 1-6AWGGround. The load center has six tandem-style 20-amp circuit breakers installed, which provides capacity for 12 individual circuits. One of the circuits is a spare. A jumper has been installed between the bus bars in the load center so that it operates at 120V. ATTACHMENT 1 Item 9.e. - Page 3 IRJ Engineers, Inc.      Mechanical & Electrical Engineers Mr. Reichmuth September 5, 2017 IRJ Job No. 1727-00 Page 2 Arroyo Grande - Reservoir 2 Emergency Generator Replacement MECHANICAL AND ELECTRICAL ENGINEERING SERVICES FURNISHED BY OR UNDER THE DIRECTION OF PROFESSIONAL ENGINEERS MEMBER OF THE AMERICAN COUNCIL OF ENGINEERING COMPANIES − CALIFORNIA The load center supplies a dedicated branch-circuit to the equipment room lights/general purpose receptacles, six ceiling mounted receptacles for the floor-mounted two-post racks, the chlorinator system and associated pump, the tank cathodic protection system, and the tank mixer. There is also a circuit routed above the ceiling in the equipment room, however, the load served was not visible from the equipment room. The two-post rack installation facilitates upgrading the communication equipment in response to improvements in technology. The load for each rack will vary depending on the installed equipment. The chlorination system includes a 120V, 1.5 horsepower pump motor. The nameplate on the motor indicates 18.2 amps at 120V. This exceeds the current rating of the 4kW generator. The operation of this motor likely contributed to the failure of the existing generator, if it operated when the generator was providing power. The existing branch-circuit feeding the chlorination system is protected by a 20-amp circuit breaker. This breaker would not typically account for the starting current of a 1.5HP motor that is started by an across-the-line contactor. If the system has experienced nuisance tripping of this circuit breaker, replacing the breaker with a larger device should address the issue. The fuel source for the existing generator is a 250-gallon liquid propane gas tank located adjacent to the generator. The following items identify where the existing installation should be upgraded to comply with Electrical Code requirements. 1. The 4-AWG phase conductor from the main circuit breaker to the ATS is rated to carry 85A and is not protected by the 100A circuit breaker. 2. The two-post racks on the west side of the equipment room impinge on the code required working clearance for the ATS. 3. The 12AWG conductors serving the chlorination system are rated to carry 20 amps. The minimum circuit ampacity required for the 1.5HP motor is 25 amps. These conductors will require replacement. 4. Many of the existing conduits do not have code required supports installed. 5. The panel directory in the load center does not identify the loads served by each circuit. RECOMMENDATIONS We recommend replacing the failed generator with a new 10kW, 120/240V unit along with a new 100-amp, 120/240V, 2-pole automatic transfer switch. The generator will need a unit mounted 2-pole circuit breaker rated 50 amps. The feeder from the generator should be 3- 8AWG & 1-8AWGGround. A new 3-2AWG & 1-8AWGGround feeder is recommended from the main circuit breaker to the ATS for the normal source. We have attached data sheets for a generator and ATS manufactured by Kohler that are representative of the materials that we suggest be used. Item 9.e. - Page 4 IRJ Engineers, Inc.      Mechanical & Electrical Engineers Mr. Reichmuth September 5, 2017 IRJ Job No. 1727-00 Page 3 Arroyo Grande - Reservoir 2 Emergency Generator Replacement MECHANICAL AND ELECTRICAL ENGINEERING SERVICES FURNISHED BY OR UNDER THE DIRECTION OF PROFESSIONAL ENGINEERS MEMBER OF THE AMERICAN COUNCIL OF ENGINEERING COMPANIES − CALIFORNIA The existing liquid propane gas tank is adequate to provide more than 24 hours of full load generator operation at minimum ambient temperature and with the tank filled to 80% of its volume. It would be desirable to provide a new 16-circuit load center as part of the new ATS installation. This arrangement would provide some added circuit space for future equipment. The existing load center can be reused if preferred, however, the jumper between the bus bars will need to be removed so that the new three wire feeder from the new ATS can be connected. A new feeder would be required from the load side of the new ATS to the existing load center. The installing contractor should ensure that a main bonding jumper between the equipment ground connection and the grounded conductor at the generator has not been installed so that the generator is not connected as a separately derived source. We suggest locating the new ATS/load center on the south wall of the equipment room between the rows of two-post racks. Branch-circuits from the new load center can be arranged to intercept the existing circuits at locations within the equipment room to facilitate transition to the new load center. A control method to prevent the chlorination system from operating when power is supplied by the generator will need to be added. Our opinion of probable construction cost to install the new generator, ATS/load center, and intercept the existing branch-circuits is $5,750. This includes a $500 allowance for modifications to the existing concrete generator pad to accommodate the new generator. The opinion of probable construction cost does not include the purchase of the generator and ATS/load center. Also, the cost of any upgrades to the existing installation where code deficiencies have been identified is not included. Please let us know if you have any questions or if the City will need assistance with design of the generator replacement. Sincerely, Jill E. Johnson, E15149 Item 9.e. - Page 5 Models:10/12RESVL Multi-Fuel LPG/Natural Gas Standard Features D DC2 Controller d One digital controller manages both the generator set and Model RXT transfer switch functions d Designed for today’s most sophisticated electronics. d Electronic speed control responds quickly to varying household demand. d Digital voltage regulation protects your sensitive electronics from harmonic distortion and unstable power quality. d Two-line, backlit LCD display is easy to read, even in direct sunlight or low light. d OnCuer Plus Generator Management System for remote monitoring is included with every generator. D Kohler Engine Features d Kohler Series 7000 V-twin engine with efficient OHV design d Powerful, reliable air-cooled performance d Simple field conversion between natural gas and LPG fuels while maintaining emission certification D Designed for Easy Installation d Steel base d Hinged, locking roof d Fuel and electrical connections through the enclosure wall eliminate the need for stub-ups through the bottom d Accepts natural gas fuel pressure as low as 3.5 inches d Load connection terminal block allows easy field wiring d Designed for outdoor installation only D Approved for stationary standby applications in locations served by a reliable utility source D Meets 181 mph wind rating D Model RXT Transfer Switch d 100 amp ATS w/NEMA 1 enclosure with 12-space load center for indoor installation is included d See page 4 for additional information D Certifications d Meets emission regulations for U.S. Environmental Protection Agency (EPA) 40 CFR 60 stationary source standards with both LPG and natural gas. Note:CARB does not regulate emergency standby generators outputting less than 50 HP. Only the EPA standards apply. d UL 2200 listed (60 Hz model) d Accepted by the Massachusetts Board of Registration of Plumbers and Gas Fitters. The Kohler r Advantage D High Quality Power Kohler home generators provide advanced voltage and frequency regulation along with ultra-low levels of harmonic distortion for excellent generator power quality to protect your valuable electronics. D Extraordinary Reliability Kohler is known for extraordinary reliability and performance and backs that up with a 5-year or 2000 hour limited warranty. D Perfect for Tight Lot Lines Can be placed as close as 18 inches from your home or small business, providing installation flexibility even on smaller lots. (Only applies to engine specification numbers GM88347-GA11, GM88347-GA12, or higher. Check state and local codes for minimum required distance from a structure.) D Powerful Performance Exclusive Powerboostt technology provides excellent starting power.The Kohler 12 kW generator can easily startandruna5tonairconditioner with up to 5 kW preload.* D Enclosure Bold new Kohler design in steel, dipped in e-coat for extra corrosion protection and painted with a durable powder coat finish D Quiet Operation Kohler home generators provide quiet, neighborhood- friendly performance. G4-255 (10/12RESVL) 6/15 Generator Ratings Model Voltage Phase Hz Alternator Standby Ratings Natural Gas LPG kW/kVA Amps kW/kVA Amps 10RESVL 120/240 1 60 2F3 9/9 37.5 10/10 41.7 12RESVL 120/240 1 60 2F4 11/11 45.8 12/12 50 RATINGS: Standbyratingsapplytoinstallationsservedbyareliableutilitysource.Allsingle-phaseunitsareratedat1.0powerfactor. Thestandbyratingisapplicabletovariableloadswithanaverage loadfactorof80%forthedurationofthepoweroutage. Nooverloadcapacity isspecifiedatthisrating. RatingsareinaccordancewithISO--3046/1,BS5514,AS2789,andDIN6271.GENERALGUIDE- LINESFORDERATING:ALTITUDE:Derate4%per305m(1000 ft.)elevation above153m(500 ft.).TEMPERATURE: Derate2%per 5.5_C(10_F)temperatureincreaseabove16_C(60_F). Avail- abilityissubjecttochangewithoutnotice. Thegeneratorsetmanufacturerreservestherighttochangethedesignorspecificationswithoutnotice andwithoutanyobligationorliabilitywhatsoever. Con- tact your local Kohler Co. generator distributor for availability. * Check the appliance manufacturer’s specifications for actual power requirements. Consult a Kohlerr Power Systems professional to calculate your exact residential power system requirements.Item 9.e. - Page 6 G4-255 (10/12RESVL) 6/15 Alternator Specifications Alternator Specifications Specifications PowerBoostt Generator 1-Phase Manufacturer Kohler Output reconnectable 120/240 Type 2-Pole, Rotating Field Leads, quantity 4 Voltage regulator Digital Insulation:NEMA MG1-1.66 Material Class H Temperature rise Class H Bearing: quantity, type 1, Sealed Ball Coupling Direct Amortisseur windings Full Voltage regulation, no-load to full-load RMS ±1.0% One-step load acceptance 100% of Rating Peak motor starting kVA:(35% dip for voltages below) 240 V, 2F3 (60 Hz)16.8 240 V, 2F4 (60 Hz)20.3 Alternator Features D Compliance with NEMA, IEEE, and ANSI standards for temperature rise D Self-ventilated and dripproof construction D Windings are vacuum-impregnated with epoxy varnish for dependability and long life. D Superior voltage waveform and minimum harmonic distortion from skewed alternator construction D Digital voltage regulator with 1.0% no-load to full-load RMS regulation D Rotating-field alternator with static exciter for excellent load response D Total harmonic distortion (THD) from no load to full load with a linear load is less than 5%. Application Data Engine Engine Specifications 10RESVL 12RESVL Manufacturer Kohler Engine: model, type KT725 Cylinder arrangement V-2 Displacement, cm 3 (cu. in.)725 (44) Bore and stroke, mm (in.)83 x 67 (3.3 x 2.6) Compression ratio 9.0:1 Main bearings: quantity, type 2, Parent Material Rated RPM 60 Hz 3600 Max. engine power at rated rpm, kW (HP) LPG, 60 Hz 16 (21.4) Natural gas, 60 Hz 13.4 (18) Cylinder head material Aluminum Valve material Steel/Stelliter Piston type and material Aluminum Alloy Crankshaft material Heat Treated, Ductile Iron Governor: type Electronic Frequency regulation, no load to full load Isochronous Frequency regulation, steady state 1.0% Air cleaner type Dry Exhaust Exhaust System 10RESVL 12RESVL Exhaust temperature exiting the enclosure at rated kW, dry,_C(_F)106 (224)106 (224) Engine Electrical Engine Electrical System 10RESVL 12RESVL Ignition system Electronic, Capacitive Discharge Starter motor rated voltage (DC)12 Battery (purchased separately): Ground Negative Volts (DC)12 Battery quantity 1 Recommended cold cranking amps: (CCA) rating for --18_C(0_F)500 Group size 51 Lubrication Lubricating System 10RESVL 12RESVL Type Full Pressure Oil capacity (with filter), L (qt.) *1.9 (2.0) Oil filter: quantity, type 1, Cartridge * Oil capacity for a new, dry engine. Fuel Pipe Size Minimum Gas Pipe Size Recommendation, in. NPT Pipe Length, m (ft.) 10RESVL 12RESVL Natural Gas 179,000 Btu/hr. LPG 222,500 Btu/hr. Natural Gas 216,000 Btu/hr. LPG 257,500 Btu/hr. 8 (25)3/4 3/4 3/4 3/4 15 (50) 1 3/4 1 1 30 (100) 1 1 1-1/4 1 46 (150) 1 1/4 1 1-1/4 1 1/4 61 (200) 1 1/4 1 1/4 1 1/4 1 1/4 Item 9.e. - Page 7 G4-255 (10/12RESVL) 6/15 Fuel Requirements Fuel System 10RESVL 12RESVL Fuel types Natural Gas or LPG Fuel supply inlet 1/2 NPT Fuel supply pressure, kPa (in. H2O): Natural gas .87--2.7 (3.5-11) LP 1.7--2.7 (7-11) Fuel Composition Limits *Nat. Gas LPG Methane, % by volume (minimum)90 min.— Ethane, % by volume (maximum) 4.0 max. — Propane, % by volume 1.0 max. 85 min. Propene, % by volume (maximum) 0.1 max. 5.0 max. C4 and higher, % by volume 0.3 max. 2.5 max. Sulfur, ppm mass (maximum)25 max. Lower heating value, MJ/m3 (Btu/ft3), (minimum)33.2 (890) 84.2 (2260) * Contact your local distributor for suitability and rating derates based on fuel compositions outside these limits. Operation Requirements Fuel Consumption Model Fuel Type % Load Fuel Consumption, m 3/hr. (cfh) 10RESVL Natural Gas 100 5.1 (179) 75 4.1 (145) 50 3.4 (120) 25 2.7 (97) Exercise 2.1 (75) LPG 100 2.5 (89) 75 2.0 (69) 50 1.5 (52) 25 1.1 (39) Exercise 0.8 (29) 12RESVL Natural Gas 100 6.1 (216) 75 4.5 (160) 50 3.6 (128) 25 2.8 (99) Exercise 2.1 (74) LPG 100 2.9 (103) 75 2.2 (76) 50 1.6 (57) 25 1.2 (42) Exercise 0.8 (30) Nominal fuel rating: Natural gas: 37 MJ/m 3 (1000 Btu/ft. 3) LPG: 93 MJ/m 3 (2500 Btu/ft. 3) LPG conversion factors: 8.58 ft. 3 =1lb. 0.535 m 3 =1kg 36.39 ft. 3 = 1 gal. Sound Data Model 10RESVL and 12RESVL 8 point logarithmic average sound levels are 67 dB(A) during weekly engine exercise and 71 dB(A) during full-speed generator diagnostics and normal operation. For comparison to competitor ratings, the lowest point sound levels are 64 dB(A) and 69 dB(A) respectively.* All sound levels are measured at 7 meters with no load. * Lowest of 8 points measured around the generator. Sound levels at other points around generator may vary depending on installation parameters. DC2 Controller Voltage: 240 V Freq: 60.0 Hz Voltage: 240 V Freq: 60.0 Hz The DC2 controller provides integrated control for the generator set, Kohlerr Model RXT transfer switch, programmable interface module (PIM). The DC2 controller’s 2-line LCD screen provides a clear, easy-to-read display of status messages, even in direct sunlight or low light. DC2 Controller Features D OFF, AUTO, RUN, and EXERCISE pushbuttons D LED indicators for OFF, AUTO, RUN, and EXERCISE modes D LCD display d Two lines x 16 characters per line d Backlit display with adjustable contrast for excellent visibility in all lighting conditions D Scrolling system status display d Generator set status d Voltage and frequency d Engine temperature d Oil pressure d Battery voltage d Engine runtime hours d Maintenance reminders d OnCuer Plus status (connected/disconnected) D Date and time displays D Smart engine cooldown senses engine temperature D Digital isochronous governor to maintain steady-state speed at all loads D Digital voltage regulation:±1.0% RMS no-load to full-load D Automatic start with programmed cranking cycle D Exercise modes d Unloaded weekly exercise with complete system diagnostics d Unloaded full-speed exercise d Loaded full-speed exercise (Model RXT ATS required) D Front-access mini USB connector for SiteTecht or USB Utility connection D Integral Ethernet connector for Kohlerr OnCuer Plus D Built-in 2.5 amp battery charger D Remote two-wire start/stop capability for optional connection of Model RDT transfer switches D Diagnostic messages d Displays diagnostic messages for the engine, generator, Model RXT transfer switch, programmable interface module (PIM) d Over 70 diagnostic messages can be displayed D A laptop computer and Kohlerr SiteTecht software can be used to change system settings or upgrade controller firmware. Item 9.e. - Page 8 2015 by Kohler Co. All rights reserved. DISTRIBUTED BY: Generator Set Dimensions and Weights Overall Size, L x W x H:777 x 712 x 824 mm (30.6 x 28 x 32.4 in.) Shipping Weight: 10RESVL w/ATS 203 kg (448 lb.) 12RESVL w/ATS 205 kg (453 lb.) NOTE: Dimensions are provided for reference only and should not be used for planning installation. Contact your local distributor for more detailed information. L W H G4-255 (10/12RESVL) 6/15 Generator Set Standard Features D ATS: Model RXT automatic transfer switch with indoor enclosure and 12-circuit load center D Battery cables D Flexible fuel line D Critical silencer D DC2 generator set/ATS controller D EPA certified fuel system D Field-connection terminal block D Fuel solenoid valve and secondary regulator D Line circuit breaker: 10RESVL: 50 amps 12RESVL: 60 amps D Multi-fuel system, LPG/natural gas, field-convertible D Oil drain extension with shutoff valve D OnCuer Plus Generator Management System D Rodent-resistant construction D Sound enclosure with sound-deadening, flame-retardant foam per UL 94, class HF-1 D 5-year limited warranty Model RXT Transfer Switch D 100 amp RXT with 12-space load center and NEMA 1 steel enclosure for indoor installation D UL listed D 240 VAC/60 Hz D Withstand rating 10,000 amps with specified breakers D Designed for use only with Kohlerr generator sets equipped with the RDC2 or DC2 controller D See RXT Specification Sheet for more information Available Accessories Concrete Mounting Pads -Concrete mounting pad, 3 in. thick -Concrete mounting pad, 4 in. thick (recommended for storm-prone areas) Available Accessories, Continued Controller Accessories -Programmable Interface Module (PIM) (provides 2 digital inputs and 6 relay outputs) Electrical System -Battery Maintenance -Maintenance kit Literature -General maintenance literature kit -Overhaul literature kit -Production literature kit Starting Aids -Carburetor heater, 120 VAC (recommended for reliable starting at temperatures below 0_C[32_F]) Miscellaneous Accessories -__________________________________________ -__________________________________________ * Accessories are available through Kohler authorized distributors and dealers. KOHLER CO., Kohler, Wisconsin 53044 USA Phone 920-457-4441, Fax 920-459-1646 For the nearest sales and service outlet in the US and Canada, phone 1-800-544-2444 KOHLERPower.com Kohler Power Systems Asia Pacific Headquarters 7 Jurong Pier Road Singapore 619159 Phone (65) 6264-6422, Fax (65) 6264-6455 Item 9.e. - Page 9 MKN & Associates, Inc.  P O Box 1604  Arroyo Grande CA 93421  805 904 6530  Reservoir 2 Emergency Generator Replacement Project‐ Design and Construction Phase Proposal   September 15, 2017  Shane Taylor  Utilities Manager  City of Arroyo Grande  (Submitted Electronically)  RE: Reservoir 2 Emergency Generator Replacement Project‐ Design and Construction Phase Services  Dear Shane, MKN has prepared a scope of work to provide construction documents and construction phase services  for the City to replace the Reservoir 2 emergency generator.   SCOPE OF WORK  Draft and Final Construction Documents  Because the project construction costs are expected to be less than $6,000 the City will obtain quotes  from three contractors using the City’s “Request for Quotes” process. MKN will edit the City’s “Request  for Quotes” documents for the proposed project. It has been assumed that a site plan with connection  and layout details will be required to provide the Contractor with sufficient information to bid and perform  the work.  The project will include installation of an owner furnished emergency generator, automatic  transfer switch, installation of a new load center, reconnection of the existing branch circuits, and  implementation of a control scheme to shed the chlorination system when power is provided by the  generator. We anticipate providing the following exhibits for the project:  Site Plan including location of owner‐supplied generator and connection points Connection details Wiring and conduit details Drawings will be prepared as 11‐inch x 17‐inch sheets. The City’s Request for Quotes documents will be  revised for the project. MKN will provide a project bid schedule for the City’s use.  One copy of electronic specifications saved as PDF files, with drawings, will be provided to the City for  review at the draft design submittal. The final construction contract documents will be signed and sealed  by a registered professional engineer licensed in the State of California and will be provided in electronic  format. An Engineer’s Opinion of Construction Cost will be provided with the draft and final plans and  specifications.  Bid Phase Services  During bidding of the project MKN will provide the following services:  ATTACHMENT 2 Item 9.e. - Page 10 Shane Taylor  Page 2 Reservoir 2 Emergency Generator Replacement Project‐ Design and Construction Phase Proposal   Respond to requests for information (RFIs) during the bidding period and prepare addenda for issuance to bidders by the City. Review submitted bids. Construction Phase Services  During construction of the project MKN will provide the following services:  MKN and/or IRJ will attend a pre‐construction conference with the City and Contractor. MKN will review and respond to two (2) RFIs. IRJ will provide two (2) site visits to observe the Contractors progress and for general conformance with the design documents. MKN will prepare record drawings based on the Contractor’s redlines ASSUMPTIONS:  The City will be procuring and purchasing the generator and automatic transfer switch. The chlorine pump and tank mixing system is not required to operate when the emergency generator is on. MKN shall be entitled to rely reasonably upon the accuracy of data and information provided by or through Client and will use good professional judgment in reviewing and evaluating such information. If MKN identifies any error or inaccuracy in data or information provided by or through Client, or determines that additional data or information is needed to perform the services, MKN shall promptly notify the client. BUDGET  MKN proposes to complete this work on a time and material basis with a budget not to exceed $9,870.  Hourly rates are attached but may be revised annually. Other direct costs will be charged with a 10%  markup.   Project Task Budget  Construction Documents MKN  $1,101  IRJ $5,280  Bid and Construction Phase Services   MKN $   516  IRJ $2,640  Total $9,537  Thank you for providing MKN with the opportunity to provide professional services for your project. If you  have any questions regarding this proposal, please let me know.  Sincerely,   J.J. Reichmuth, PE  Project Manager   Item 9.e. - Page 11 798 Francis Avenue, San Luis Obispo, CA 93401 805.543.4643 Fax 805.543.4673 Gens@SanLuisPowerhouse.com Equipment Sales Quotation Date: September 8, 2017 To: City of Arroyo Grande, Shane Taylor Subject: Kohler generator & ATS quote Message: Please find below the quotation you requested. 1- Kohler 10RESV, 120/240VAC, LP, housed gen. $3,130.00 1- Kohler RXT100 nema 1R/3R automatic transfer sw. 555.00 Starting battery 121.95 Estimated frt. 195.00 Taxable Sub-total 4,001.95 Factory Certified on-site start up 650.00 State Sale Tax, if applicable 310.15 Estimated Total $4,962.10* *Price does not include installation of any kind. Please call if you have any questions. If this estimated meets your approval please sign and date below, scan and email back. Approved by: ______________________________Date__________ Thanks By: Russ Kimmell ATTACHMENT 3 Item 9.e. - Page 12