CC 2017-10-10_09e Reservoir No 2 Standby Generator
MEMORANDUM
TO: CITY COUNCIL
FROM: BILL ROBESON, PUBLIC WORKS DIRECTOR
BY: SHANE TAYLOR, UTILITIES MANAGER
SUBJECT: CONSIDERATION OF AN APPROPRIATION OF FUNDS TO REPLACE
THE EMERGENCY STANDBY GENERATOR LOCATED AT
RESERVOIR NO. 2 ON HILLCREST DRIVE
DATE: OCTOBER 10, 2017
SUMMARY OF ACTION:
Approve funds to replace the generator at Reservoir No. 2.
IMPACT ON FINANCIAL AND PERSONNEL RESOURCES:
The replacement generator was not budgeted in FY 2017/18 and will reduce the
General Fund balance by $25,000.
RECOMMENDATION:
It is recommended the City Council approve an appropriation of $25,000 from the
unappropriated General Fund Balance to purchase a new standby generator and
automatic transfer switch for the Reservoir No. 2 communication building.
BACKGROUND:
The radio communication building located at Reservoir No. 2 on Hillcrest Drive provides
a secure location for the radios that serve the Arroyo Grande Police Department, Five
Cities Fire Authority, and the Public Works Department. Radio communication is vital to
daily operations. The existing standby generator is over 30 years old and no longer
works. A temporary trailer mounted generator with manual start has been in place since
the old generator stopped working during the February 2017 storm. It is vital during
power outages that this building has power to continue radio communications.
ANALYSIS OF ISSUES:
The existing propane powered standby generator at Reservoir No. 2 needs to be
replaced. A report was prepared by IRJ Engineers, Inc. detailing the requirements for
the replacement generator and automatic transfer switch. The report also identified
deficiencies in the current circuits that should also be corrected. The replacement and
upgrade of equipment will provide a long term solution to the current and future power
needs of this facility.
Item 9.e. - Page 1
CITY COUNCIL
CONSIDERATION OF AN APPROPRIATION OF FUNDS TO REPLACE THE
EMERGENCY STANDBY GENERATOR LOCATED AT RESERVOIR NO. 2 ON
HILLCREST DRIVE
OCTOBER 10, 2017
PAGE 2
ALTERNATIVES:
The following alternatives are provided for the Council’s consideration:
1. Authorize the appropriation of funds to purchase the new standby generator;
2. Do not authorize the appropriation of funds;
3. Provide direction to staff.
ADVANTAGES:
The radio communication building will have reliable power during power outages.
DISADVANTAGES:
The purchase and installation of the new standby generator will reduce the General
Fund by $25,000.
ENVIRONMENTAL REVIEW:
The project is categorically exempt from the California Environmental Quality Act
(CEQA) pursuant to CEQA Guidelines Section 15301 covering minor alteration of
mechanical equipment.
PUBLIC NOTIFICATION AND COMMENTS:
The Agenda was posted at City Hall and on the City’s website in accordance with
Government Code Section 54954.2.
Attachment:
1. Letter Report from IRJ Engineers, Inc. dated September 5, 2017
2. Letter from MKN & Associates, Inc. regarding Design and Construction Phase
Services dated September 15, 2017
3. Generator Sales Quotation from San Luis Powerhouse dated September 8, 2017
Item 9.e. - Page 2
OFFICERS
JACK V. IVERS, P.E.
STEVEN ROMOFSKY, P.E.
JILL E. JOHNSON, P.E.
IRJ ENGINEERS INC.
MECHANICAL & ELECTRICAL ENGINEERS
2497 E. HARBOR BOULEVARD, SUITE 1 VENTURA, CALIFORNIA 93001-3933
TELE (805) 642-2355 FAX (805) 658-0623
MECHANICAL AND ELECTRICAL ENGINEERING SERVICES FURNISHED BY OR UNDER THE DIRECTION OF PROFESSIONAL ENGINEERS
MEMBER OF THE AMERICAN COUNCIL OF ENGINEERING COMPANIES − CALIFORNIA
September 5, 2017
Mr. J.J. Reichmuth
Michael K. Nunley & Associates
P.O. Box 1604
Arroyo Grande, California 93421
Re: City of Arroyo Grande
Reservoir 2 Emergency Generator Replacement
Letter Report
Dear J.J.:
We reviewed the existing emergency generator installation at Reservoir 2 on August 15, 2017.
The following report describes our observations and recommendations.
OBSERVATIONS
The existing system is served by a 100-amp, 120/240V, single-phase, three-wire service from
PG&E to a 100-amp, 2-pole meter/main circuit breaker enclosure mounted on the building
exterior. There is an existing 120/240V, single-phase, three-wire, 4kW backup generator that
supplies emergency power through a 30-amp, 1-pole circuit breaker mounted on the generator.
The generator nameplate lists the rated amperes at 16.7. The 30-amp breaker is too large to
provide overcurrent protection for the generator, and should have been a 2-pole device. It does
not appear that the existing generator was properly sized for the loads that it supplied.
The main circuit breaker and generator breaker supply the normal and emergency sources,
respectively, to a 30-amp, 120V automatic transfer switch (ATS) located in the equipment room.
It is unclear why a 1-pole, 2-wire ATS was selected for this installation. The 100-amp main
circuit breaker does not provide code compliant overcurrent protection for the ATS when power
is supplied by the utility.
The feeder between the main circuit breaker and the ATS is 2-4AWG & 1-6AWGGround. The
feeder between the generator breaker and the ATS is 2-12AWG & 1-12AWGGround. Although
both the utility service and the generator are rated for 120/240V, single-phase, three-wire
operation, they are both connected so that only one phase is used. It is very unusual to connect
this equipment at 120V in lieu of 120/240V.
The ATS load side feeds a 100-amp, 120/240V load center located inside the equipment room
via 2-4AWG & 1-6AWGGround. The load center has six tandem-style 20-amp circuit breakers
installed, which provides capacity for 12 individual circuits. One of the circuits is a spare. A
jumper has been installed between the bus bars in the load center so that it operates at 120V.
ATTACHMENT 1
Item 9.e. - Page 3
IRJ Engineers, Inc.
Mechanical & Electrical Engineers
Mr. Reichmuth
September 5, 2017 IRJ Job No. 1727-00
Page 2 Arroyo Grande - Reservoir 2 Emergency Generator Replacement
MECHANICAL AND ELECTRICAL ENGINEERING SERVICES FURNISHED BY OR UNDER THE DIRECTION OF PROFESSIONAL ENGINEERS
MEMBER OF THE AMERICAN COUNCIL OF ENGINEERING COMPANIES − CALIFORNIA
The load center supplies a dedicated branch-circuit to the equipment room lights/general
purpose receptacles, six ceiling mounted receptacles for the floor-mounted two-post racks, the
chlorinator system and associated pump, the tank cathodic protection system, and the tank
mixer. There is also a circuit routed above the ceiling in the equipment room, however, the load
served was not visible from the equipment room.
The two-post rack installation facilitates upgrading the communication equipment in response to
improvements in technology. The load for each rack will vary depending on the installed
equipment.
The chlorination system includes a 120V, 1.5 horsepower pump motor. The nameplate on the
motor indicates 18.2 amps at 120V. This exceeds the current rating of the 4kW generator. The
operation of this motor likely contributed to the failure of the existing generator, if it operated
when the generator was providing power. The existing branch-circuit feeding the chlorination
system is protected by a 20-amp circuit breaker. This breaker would not typically account for
the starting current of a 1.5HP motor that is started by an across-the-line contactor. If the
system has experienced nuisance tripping of this circuit breaker, replacing the breaker with a
larger device should address the issue.
The fuel source for the existing generator is a 250-gallon liquid propane gas tank located
adjacent to the generator.
The following items identify where the existing installation should be upgraded to comply with
Electrical Code requirements.
1. The 4-AWG phase conductor from the main circuit breaker to the ATS is rated to carry
85A and is not protected by the 100A circuit breaker.
2. The two-post racks on the west side of the equipment room impinge on the code
required working clearance for the ATS.
3. The 12AWG conductors serving the chlorination system are rated to carry 20 amps. The
minimum circuit ampacity required for the 1.5HP motor is 25 amps. These conductors
will require replacement.
4. Many of the existing conduits do not have code required supports installed.
5. The panel directory in the load center does not identify the loads served by each circuit.
RECOMMENDATIONS
We recommend replacing the failed generator with a new 10kW, 120/240V unit along with a
new 100-amp, 120/240V, 2-pole automatic transfer switch. The generator will need a unit
mounted 2-pole circuit breaker rated 50 amps. The feeder from the generator should be 3-
8AWG & 1-8AWGGround. A new 3-2AWG & 1-8AWGGround feeder is recommended from the
main circuit breaker to the ATS for the normal source. We have attached data sheets for a
generator and ATS manufactured by Kohler that are representative of the materials that we
suggest be used.
Item 9.e. - Page 4
IRJ Engineers, Inc.
Mechanical & Electrical Engineers
Mr. Reichmuth
September 5, 2017 IRJ Job No. 1727-00
Page 3 Arroyo Grande - Reservoir 2 Emergency Generator Replacement
MECHANICAL AND ELECTRICAL ENGINEERING SERVICES FURNISHED BY OR UNDER THE DIRECTION OF PROFESSIONAL ENGINEERS
MEMBER OF THE AMERICAN COUNCIL OF ENGINEERING COMPANIES − CALIFORNIA
The existing liquid propane gas tank is adequate to provide more than 24 hours of full load
generator operation at minimum ambient temperature and with the tank filled to 80% of its
volume.
It would be desirable to provide a new 16-circuit load center as part of the new ATS installation.
This arrangement would provide some added circuit space for future equipment. The existing
load center can be reused if preferred, however, the jumper between the bus bars will need to
be removed so that the new three wire feeder from the new ATS can be connected. A new
feeder would be required from the load side of the new ATS to the existing load center.
The installing contractor should ensure that a main bonding jumper between the equipment
ground connection and the grounded conductor at the generator has not been installed so that
the generator is not connected as a separately derived source.
We suggest locating the new ATS/load center on the south wall of the equipment room between
the rows of two-post racks. Branch-circuits from the new load center can be arranged to
intercept the existing circuits at locations within the equipment room to facilitate transition to the
new load center.
A control method to prevent the chlorination system from operating when power is supplied by
the generator will need to be added.
Our opinion of probable construction cost to install the new generator, ATS/load center, and
intercept the existing branch-circuits is $5,750. This includes a $500 allowance for
modifications to the existing concrete generator pad to accommodate the new generator. The
opinion of probable construction cost does not include the purchase of the generator and
ATS/load center. Also, the cost of any upgrades to the existing installation where code
deficiencies have been identified is not included.
Please let us know if you have any questions or if the City will need assistance with design of
the generator replacement.
Sincerely,
Jill E. Johnson, E15149
Item 9.e. - Page 5
Models:10/12RESVL
Multi-Fuel
LPG/Natural Gas
Standard Features
D DC2 Controller
d One digital controller manages both the generator set
and Model RXT transfer switch functions
d Designed for today’s most sophisticated electronics.
d Electronic speed control responds quickly to varying
household demand.
d Digital voltage regulation protects your sensitive
electronics from harmonic distortion and unstable power
quality.
d Two-line, backlit LCD display is easy to read, even in
direct sunlight or low light.
d OnCuer Plus Generator Management System for
remote monitoring is included with every generator.
D Kohler Engine Features
d Kohler Series 7000 V-twin engine with efficient OHV
design
d Powerful, reliable air-cooled performance
d Simple field conversion between natural gas and LPG
fuels while maintaining emission certification
D Designed for Easy Installation
d Steel base
d Hinged, locking roof
d Fuel and electrical connections through the enclosure
wall eliminate the need for stub-ups through the bottom
d Accepts natural gas fuel pressure as low as 3.5 inches
d Load connection terminal block allows easy field wiring
d Designed for outdoor installation only
D Approved for stationary standby applications in locations
served by a reliable utility source
D Meets 181 mph wind rating
D Model RXT Transfer Switch
d 100 amp ATS w/NEMA 1 enclosure with 12-space load
center for indoor installation is included
d See page 4 for additional information
D Certifications
d Meets emission regulations for U.S. Environmental
Protection Agency (EPA) 40 CFR 60 stationary source
standards with both LPG and natural gas.
Note:CARB does not regulate emergency standby
generators outputting less than 50 HP. Only the EPA
standards apply.
d UL 2200 listed (60 Hz model)
d Accepted by the Massachusetts Board of Registration of
Plumbers and Gas Fitters.
The Kohler
r Advantage
D High Quality Power
Kohler home generators provide advanced voltage and
frequency regulation along with ultra-low levels of
harmonic distortion for excellent generator power quality to
protect your valuable electronics.
D Extraordinary Reliability
Kohler is known for extraordinary reliability and
performance and backs that up with a 5-year or 2000 hour
limited warranty.
D Perfect for Tight Lot Lines
Can be placed as close as 18 inches from your home or
small business, providing installation flexibility even on
smaller lots. (Only applies to engine specification numbers
GM88347-GA11, GM88347-GA12, or higher. Check state
and local codes for minimum required distance from a
structure.)
D Powerful Performance
Exclusive Powerboostt technology provides excellent
starting power.The Kohler 12 kW generator can easily
startandruna5tonairconditioner with up to 5 kW
preload.*
D Enclosure
Bold new Kohler design in steel, dipped in e-coat for extra
corrosion protection and painted with a durable powder
coat finish
D Quiet Operation
Kohler home generators provide quiet, neighborhood-
friendly performance.
G4-255 (10/12RESVL) 6/15
Generator Ratings
Model Voltage Phase Hz Alternator
Standby Ratings
Natural Gas LPG
kW/kVA Amps kW/kVA Amps
10RESVL 120/240 1 60 2F3 9/9 37.5 10/10 41.7
12RESVL 120/240 1 60 2F4 11/11 45.8 12/12 50
RATINGS: Standbyratingsapplytoinstallationsservedbyareliableutilitysource.Allsingle-phaseunitsareratedat1.0powerfactor. Thestandbyratingisapplicabletovariableloadswithanaverage
loadfactorof80%forthedurationofthepoweroutage. Nooverloadcapacity isspecifiedatthisrating. RatingsareinaccordancewithISO--3046/1,BS5514,AS2789,andDIN6271.GENERALGUIDE-
LINESFORDERATING:ALTITUDE:Derate4%per305m(1000 ft.)elevation above153m(500 ft.).TEMPERATURE: Derate2%per 5.5_C(10_F)temperatureincreaseabove16_C(60_F). Avail-
abilityissubjecttochangewithoutnotice. Thegeneratorsetmanufacturerreservestherighttochangethedesignorspecificationswithoutnotice andwithoutanyobligationorliabilitywhatsoever. Con-
tact your local Kohler Co. generator distributor for availability.
* Check the appliance manufacturer’s specifications for actual power requirements. Consult a Kohlerr Power Systems professional to calculate your exact residential power system
requirements.Item 9.e. - Page 6
G4-255 (10/12RESVL) 6/15
Alternator Specifications
Alternator Specifications
Specifications
PowerBoostt Generator
1-Phase
Manufacturer Kohler
Output reconnectable 120/240
Type 2-Pole, Rotating Field
Leads, quantity 4
Voltage regulator Digital
Insulation:NEMA MG1-1.66
Material Class H
Temperature rise Class H
Bearing: quantity, type 1, Sealed Ball
Coupling Direct
Amortisseur windings Full
Voltage regulation, no-load to full-load
RMS ±1.0%
One-step load acceptance 100% of Rating
Peak motor starting kVA:(35% dip for voltages
below)
240 V, 2F3 (60 Hz)16.8
240 V, 2F4 (60 Hz)20.3
Alternator Features
D Compliance with NEMA, IEEE, and ANSI standards for
temperature rise
D Self-ventilated and dripproof construction
D Windings are vacuum-impregnated with epoxy varnish for
dependability and long life.
D Superior voltage waveform and minimum harmonic
distortion from skewed alternator construction
D Digital voltage regulator with 1.0% no-load to full-load
RMS regulation
D Rotating-field alternator with static exciter for excellent
load response
D Total harmonic distortion (THD) from no load to full load with
a linear load is less than 5%.
Application Data
Engine
Engine Specifications 10RESVL 12RESVL
Manufacturer Kohler
Engine: model, type KT725
Cylinder arrangement V-2
Displacement, cm
3 (cu. in.)725 (44)
Bore and stroke, mm (in.)83 x 67 (3.3 x 2.6)
Compression ratio 9.0:1
Main bearings: quantity, type 2, Parent Material
Rated RPM
60 Hz 3600
Max. engine power at rated rpm, kW (HP)
LPG, 60 Hz 16 (21.4)
Natural gas, 60 Hz 13.4 (18)
Cylinder head material Aluminum
Valve material Steel/Stelliter
Piston type and material Aluminum Alloy
Crankshaft material Heat Treated, Ductile Iron
Governor: type Electronic
Frequency regulation, no load to full load Isochronous
Frequency regulation, steady state 1.0%
Air cleaner type Dry
Exhaust
Exhaust System 10RESVL 12RESVL
Exhaust temperature exiting the
enclosure at rated kW, dry,_C(_F)106 (224)106 (224)
Engine Electrical
Engine Electrical System 10RESVL 12RESVL
Ignition system Electronic,
Capacitive Discharge
Starter motor rated voltage (DC)12
Battery (purchased separately):
Ground Negative
Volts (DC)12
Battery quantity 1
Recommended cold cranking amps:
(CCA) rating for --18_C(0_F)500
Group size 51
Lubrication
Lubricating System 10RESVL 12RESVL
Type Full Pressure
Oil capacity (with filter), L (qt.) *1.9 (2.0)
Oil filter: quantity, type 1, Cartridge
* Oil capacity for a new, dry engine.
Fuel Pipe Size
Minimum Gas Pipe Size Recommendation, in. NPT
Pipe
Length,
m (ft.)
10RESVL 12RESVL
Natural
Gas
179,000
Btu/hr.
LPG
222,500
Btu/hr.
Natural
Gas
216,000
Btu/hr.
LPG
257,500
Btu/hr.
8 (25)3/4 3/4 3/4 3/4
15 (50) 1 3/4 1 1
30 (100) 1 1 1-1/4 1
46 (150) 1 1/4 1 1-1/4 1 1/4
61 (200) 1 1/4 1 1/4 1 1/4 1 1/4
Item 9.e. - Page 7
G4-255 (10/12RESVL) 6/15
Fuel Requirements
Fuel System 10RESVL 12RESVL
Fuel types Natural Gas or LPG
Fuel supply inlet 1/2 NPT
Fuel supply pressure, kPa (in. H2O):
Natural gas .87--2.7 (3.5-11)
LP 1.7--2.7 (7-11)
Fuel Composition Limits *Nat. Gas LPG
Methane, % by volume (minimum)90 min.—
Ethane, % by volume (maximum) 4.0 max. —
Propane, % by volume 1.0 max. 85 min.
Propene, % by volume (maximum) 0.1 max. 5.0 max.
C4 and higher, % by volume 0.3 max. 2.5 max.
Sulfur, ppm mass (maximum)25 max.
Lower heating value,
MJ/m3 (Btu/ft3), (minimum)33.2 (890) 84.2 (2260)
* Contact your local distributor for suitability and rating derates based
on fuel compositions outside these limits.
Operation Requirements
Fuel Consumption
Model
Fuel
Type % Load Fuel Consumption, m
3/hr. (cfh)
10RESVL
Natural
Gas
100 5.1 (179)
75 4.1 (145)
50 3.4 (120)
25 2.7 (97)
Exercise 2.1 (75)
LPG
100 2.5 (89)
75 2.0 (69)
50 1.5 (52)
25 1.1 (39)
Exercise 0.8 (29)
12RESVL
Natural
Gas
100 6.1 (216)
75 4.5 (160)
50 3.6 (128)
25 2.8 (99)
Exercise 2.1 (74)
LPG
100 2.9 (103)
75 2.2 (76)
50 1.6 (57)
25 1.2 (42)
Exercise 0.8 (30)
Nominal fuel rating: Natural gas: 37 MJ/m
3 (1000 Btu/ft.
3)
LPG: 93 MJ/m
3 (2500 Btu/ft.
3)
LPG conversion factors: 8.58 ft.
3 =1lb.
0.535 m
3 =1kg
36.39 ft.
3 = 1 gal.
Sound Data
Model 10RESVL and 12RESVL 8 point logarithmic average
sound levels are 67 dB(A) during weekly engine exercise and
71 dB(A) during full-speed generator diagnostics and normal
operation. For comparison to competitor ratings, the lowest
point sound levels are 64 dB(A) and 69 dB(A) respectively.*
All sound levels are measured at 7 meters with no load.
* Lowest of 8 points measured around the generator. Sound levels at other points
around generator may vary depending on installation parameters.
DC2 Controller
Voltage: 240 V
Freq: 60.0 Hz
Voltage: 240 V
Freq: 60.0 Hz
The DC2 controller provides integrated control for the generator
set, Kohlerr Model RXT transfer switch, programmable
interface module (PIM).
The DC2 controller’s 2-line LCD screen provides a clear,
easy-to-read display of status messages, even in direct sunlight
or low light.
DC2 Controller Features
D OFF, AUTO, RUN, and EXERCISE pushbuttons
D LED indicators for OFF, AUTO, RUN, and EXERCISE modes
D LCD display
d Two lines x 16 characters per line
d Backlit display with adjustable contrast for excellent
visibility in all lighting conditions
D Scrolling system status display
d Generator set status
d Voltage and frequency
d Engine temperature
d Oil pressure
d Battery voltage
d Engine runtime hours
d Maintenance reminders
d OnCuer Plus status (connected/disconnected)
D Date and time displays
D Smart engine cooldown senses engine temperature
D Digital isochronous governor to maintain steady-state speed
at all loads
D Digital voltage regulation:±1.0% RMS no-load to full-load
D Automatic start with programmed cranking cycle
D Exercise modes
d Unloaded weekly exercise with complete system
diagnostics
d Unloaded full-speed exercise
d Loaded full-speed exercise (Model RXT ATS required)
D Front-access mini USB connector for SiteTecht or
USB Utility connection
D Integral Ethernet connector for Kohlerr OnCuer Plus
D Built-in 2.5 amp battery charger
D Remote two-wire start/stop capability for optional connection
of Model RDT transfer switches
D Diagnostic messages
d Displays diagnostic messages for the engine, generator,
Model RXT transfer switch, programmable interface
module (PIM)
d Over 70 diagnostic messages can be displayed
D A laptop computer and Kohlerr SiteTecht software can be
used to change system settings or upgrade controller
firmware.
Item 9.e. - Page 8
2015 by Kohler Co. All rights reserved.
DISTRIBUTED BY:
Generator Set Dimensions and Weights
Overall Size, L x W x H:777 x 712 x 824 mm
(30.6 x 28 x 32.4 in.)
Shipping Weight: 10RESVL w/ATS 203 kg (448 lb.)
12RESVL w/ATS 205 kg (453 lb.)
NOTE: Dimensions are provided for reference only and should not be used for planning
installation. Contact your local distributor for more detailed information.
L W
H
G4-255 (10/12RESVL) 6/15
Generator Set Standard Features
D ATS: Model RXT automatic transfer switch with indoor
enclosure and 12-circuit load center
D Battery cables
D Flexible fuel line
D Critical silencer
D DC2 generator set/ATS controller
D EPA certified fuel system
D Field-connection terminal block
D Fuel solenoid valve and secondary regulator
D Line circuit breaker:
10RESVL: 50 amps
12RESVL: 60 amps
D Multi-fuel system, LPG/natural gas, field-convertible
D Oil drain extension with shutoff valve
D OnCuer Plus Generator Management System
D Rodent-resistant construction
D Sound enclosure with sound-deadening, flame-retardant
foam per UL 94, class HF-1
D 5-year limited warranty
Model RXT Transfer Switch
D 100 amp RXT with 12-space load center and NEMA 1 steel
enclosure for indoor installation
D UL listed
D 240 VAC/60 Hz
D Withstand rating 10,000 amps with specified breakers
D Designed for use only with Kohlerr generator sets equipped
with the RDC2 or DC2 controller
D See RXT Specification Sheet for more information
Available Accessories
Concrete Mounting Pads
-Concrete mounting pad, 3 in. thick
-Concrete mounting pad, 4 in. thick
(recommended for storm-prone areas)
Available Accessories, Continued
Controller Accessories
-Programmable Interface Module (PIM)
(provides 2 digital inputs and 6 relay outputs)
Electrical System
-Battery
Maintenance
-Maintenance kit
Literature
-General maintenance literature kit
-Overhaul literature kit
-Production literature kit
Starting Aids
-Carburetor heater, 120 VAC (recommended for
reliable starting at temperatures below 0_C[32_F])
Miscellaneous Accessories
-__________________________________________
-__________________________________________
* Accessories are available through Kohler authorized distributors and
dealers.
KOHLER CO., Kohler, Wisconsin 53044 USA
Phone 920-457-4441, Fax 920-459-1646
For the nearest sales and service outlet in the
US and Canada, phone 1-800-544-2444
KOHLERPower.com
Kohler Power Systems
Asia Pacific Headquarters
7 Jurong Pier Road
Singapore 619159
Phone (65) 6264-6422, Fax (65) 6264-6455
Item 9.e. - Page 9
MKN & Associates, Inc.
P O Box 1604
Arroyo Grande CA 93421
805 904 6530
Reservoir 2 Emergency Generator Replacement Project‐ Design and Construction Phase Proposal
September 15, 2017
Shane Taylor
Utilities Manager
City of Arroyo Grande
(Submitted Electronically)
RE: Reservoir 2 Emergency Generator Replacement Project‐ Design and Construction Phase Services
Dear Shane,
MKN has prepared a scope of work to provide construction documents and construction phase services
for the City to replace the Reservoir 2 emergency generator.
SCOPE OF WORK
Draft and Final Construction Documents
Because the project construction costs are expected to be less than $6,000 the City will obtain quotes
from three contractors using the City’s “Request for Quotes” process. MKN will edit the City’s “Request
for Quotes” documents for the proposed project. It has been assumed that a site plan with connection
and layout details will be required to provide the Contractor with sufficient information to bid and perform
the work. The project will include installation of an owner furnished emergency generator, automatic
transfer switch, installation of a new load center, reconnection of the existing branch circuits, and
implementation of a control scheme to shed the chlorination system when power is provided by the
generator. We anticipate providing the following exhibits for the project:
Site Plan including location of owner‐supplied generator and connection points
Connection details
Wiring and conduit details
Drawings will be prepared as 11‐inch x 17‐inch sheets. The City’s Request for Quotes documents will be
revised for the project. MKN will provide a project bid schedule for the City’s use.
One copy of electronic specifications saved as PDF files, with drawings, will be provided to the City for
review at the draft design submittal. The final construction contract documents will be signed and sealed
by a registered professional engineer licensed in the State of California and will be provided in electronic
format. An Engineer’s Opinion of Construction Cost will be provided with the draft and final plans and
specifications.
Bid Phase Services
During bidding of the project MKN will provide the following services:
ATTACHMENT 2
Item 9.e. - Page 10
Shane Taylor
Page 2
Reservoir 2 Emergency Generator Replacement Project‐ Design and Construction Phase Proposal
Respond to requests for information (RFIs) during the bidding period and prepare addenda for
issuance to bidders by the City.
Review submitted bids.
Construction Phase Services
During construction of the project MKN will provide the following services:
MKN and/or IRJ will attend a pre‐construction conference with the City and Contractor.
MKN will review and respond to two (2) RFIs.
IRJ will provide two (2) site visits to observe the Contractors progress and for general conformance
with the design documents.
MKN will prepare record drawings based on the Contractor’s redlines
ASSUMPTIONS:
The City will be procuring and purchasing the generator and automatic transfer switch.
The chlorine pump and tank mixing system is not required to operate when the emergency generator
is on.
MKN shall be entitled to rely reasonably upon the accuracy of data and information provided by or
through Client and will use good professional judgment in reviewing and evaluating such information.
If MKN identifies any error or inaccuracy in data or information provided by or through Client, or
determines that additional data or information is needed to perform the services, MKN shall promptly
notify the client.
BUDGET
MKN proposes to complete this work on a time and material basis with a budget not to exceed $9,870.
Hourly rates are attached but may be revised annually. Other direct costs will be charged with a 10%
markup.
Project Task Budget
Construction Documents
MKN $1,101
IRJ $5,280
Bid and Construction Phase Services
MKN $ 516
IRJ $2,640
Total $9,537
Thank you for providing MKN with the opportunity to provide professional services for your project. If you
have any questions regarding this proposal, please let me know.
Sincerely,
J.J. Reichmuth, PE
Project Manager
Item 9.e. - Page 11
798 Francis Avenue, San Luis Obispo, CA 93401
805.543.4643 Fax 805.543.4673
Gens@SanLuisPowerhouse.com
Equipment Sales Quotation
Date: September 8, 2017
To: City of Arroyo Grande, Shane Taylor
Subject: Kohler generator & ATS quote
Message: Please find below the quotation you requested.
1- Kohler 10RESV, 120/240VAC, LP, housed gen. $3,130.00
1- Kohler RXT100 nema 1R/3R automatic transfer sw. 555.00
Starting battery 121.95
Estimated frt. 195.00
Taxable Sub-total 4,001.95
Factory Certified on-site start up 650.00
State Sale Tax, if applicable 310.15
Estimated Total $4,962.10*
*Price does not include installation of any kind. Please call if you
have any questions. If this estimated meets your approval please sign
and date below, scan and email back.
Approved by: ______________________________Date__________
Thanks
By: Russ Kimmell
ATTACHMENT 3